SEKO Tekna TPR600NHH1000 combines accurate solenoid diaphragm dosing with integrated pH or ORP (Redox) measurement and control. The pump can operate at constant output or automatically adjust dosing according to the deviation of the measured value from the setpoint.
The digital TPR series provides a PT100 input for temperature compensation, alarm relay, external ON/OFF and a 4–20 mA output for transmitting the measured value to a supervisory system. This version uses a PVDF head, ceramic valve balls, a PTFE diaphragm and EPDM seals.
The pump is supplied with a complete installation kit PVDF matching the selected material configuration. Individual components can also be ordered separately later.
| Max. flow rate | 7 l/h |
| Max. backpressure | 20 bar |
| Max. stroke frequency | 120/min |
| Volume per stroke | 0.35–0.97 cm³/stroke |
| Control | constant / proportional according to pH or ORP |
| pH controller range | 0–14 pH |
| ORP / Redox controller range | ±1 500 mV |
| Temperature probe input | PT100 · temperature compensation |
| External ON/OFF | YES |
| Measured-value output | 4–20 mA |
| Alarm relay | YES · repeat alarm |
| Communication | Standard |
| Power supply | 100–240 V AC, 50/60 Hz |
| Power consumption | 14–20 W |
| Protection rating | IP65 |
| External housing | Glass-fibre-reinforced PP |
| Pump head | PVDF |
| Valve balls | Ceramic |
| Diaphragm | PTFE |
| Seals | EPDM |
| Installation kit | PVDF |
| Suction / discharge | 4 × 6 mm / 4 × 7 mm |
| Dimensions (W × D × H) | 119 × 145,4 × 237,7 mm |
| Weight | 3,9 kg |
| Packaging dimensions | 285 × 185 × 240 mm |
| Priming / venting | manual |
| HS / CN code | 841350 / 84135040 |
The maximum flow rate of 7 l/h and maximum backpressure of 20 bar do not represent a single common operating point. The available flow rate decreases as backpressure increases.
The current hydraulics 600 is highlighted. The TPR range uses hydraulics 500 / 600 / 603 / 800 / 803.
| Parameter | 500 | 600 | 603 | 800 | 803 |
|---|---|---|---|---|---|
| Max. flow rate | 1.5 l/h | 7 l/h | 8 l/h | 18 l/h | 110 l/h |
| Max. backpressure | 20 bar | 20 bar | 12 bar | 16 bar | 5 bar |
| Max. strokes | 120/min | 120/min | 160/min | 300/min | 300/min |
| Suction / discharge | 4 × 6 / 4 × 7 | 4 × 6 / 4 × 7 | 4 × 6 / 4 × 6 | 4 × 6 / 4 × 6 | 8 × 12 / 8 × 12 |
Version TPR600NHH1000 uses a PVDF head, ceramic valve balls, a PTFE diaphragm and EPDM seals. Always verify chemical compatibility for the specific medium, concentration and temperature.
Check chemical compatibilityOverview of the main Tekna-series functions. TPR is distinguished by integrated pH / ORP control, PT100, alarm relay, remote ON/OFF and a 4–20 mA measured-value output.
| Function | AKS | AKL | APG | TPG | TPT | TCK | TPR |
|---|---|---|---|---|---|---|---|
| Analog control / potentiometer | ✓ | ✓ | ✓ | × | × | × | × |
| Digital interface / menu | × | × | × | ✓ | ✓ | ✓ | ✓ |
| Constant dosing | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ |
| Level control input | × | ✓ | ✓* | ✓ | ✓ | ✓ | ✓ |
| Flow sensor input | × | × | ✓* | ✓ | ✓ | ✓ | × |
| 4–20 mA input | × | × | ✓ | ✓ | ✓ | × | × |
| Pulse input / water meter | × | × | ✓ | ✓ | ✓ | × | × |
| Pulse multiplication / division | × | × | ✓ | ✓ | ✓ | × | × |
| PPM dosing | × | × | × | ✓ | ✓ | × | × |
| Timer | × | × | × | ✓ | ✓ | ✓ | × |
| Weekly timer program | × | × | × | × | × | ✓ | × |
| Batch mode | × | × | × | ✓ | ✓ | × | × |
| Statistics | × | × | × | ✓ | ✓ | × | × |
| Password protection | × | × | × | ✓ | ✓ | × | × |
| Remote Start / Stop | × | × | × | ✓ | ✓ | ✓ | ✓ |
| Integrated pH / ORP control | × | × | × | × | ✓ | × | ✓ |
| Temperature probe input | × | × | × | × | ✓ | × | ✓ |
| 4–20 mA measured-value output | × | × | × | × | × | × | ✓ |
| Alarm relay | × | × | ✓ | ✓ | × | × | ✓ |
| Programmable time relay | × | × | × | × | × | ✓ | × |
Original spare parts matching hydraulics 600 and version PVDF / EPDM. Electronics and the control panel are specific to the TPR measurement and control series.
TPR has the controller integrated in the pump, while the measuring probe and its process installation are selected according to the application. Typical components for a complete pH / ORP control loop are shown below.
SEKO builds the TPR ordering code from seven fields. The configuration of this pump TPR600NHH1000 is highlighted in blue.
| Field 1 · Model | |
|---|---|
| TPR | Digital dosing pump with integrated pH / ORP controller |
| Field 2 · Hydraulics | |||||
|---|---|---|---|---|---|
| Code | Max. pressure | Max. flow | Strokes/min | Suction | Discharge |
| 500 | 20 bar | 1.5 l/h | 120 | 4/6 | 4/7 |
| 600 | 20 bar | 7 l/h | 120 | 4/6 | 4/7 |
| 603 | 12 bar | 8 l/h | 160 | 4/6 | 4/6 |
| 800 | 16 bar | 18 l/h | 300 | 4/6 | 4/6 |
| 803 | 5 bar | 110 l/h | 300 | 8/12 | 8/12 |
| Field 3 · Power supply | |
|---|---|
| N | 100–240 V AC, 50/60 Hz |
| Field 4 · Liquid end | ||||
|---|---|---|---|---|
| Code | Body | Connection | Balls | Diaphragm |
| H | PVDF | PVDF | Ceramic | PTFE |
| A | PVDF · AUTO DEGAS | PVDF | Ceramic | PTFE |
| I | AISI 316L | AISI 316L | AISI 316L | PTFE |
| Field 5 · Installation kit | |
|---|---|
| H | PVDF |
| P | PVDF-T |
| X | PVDF + 1.5 bar injection valve |
| 0 | Without installation kit · AISI 316L only |
| Field 6 · Seals | |
|---|---|
| 0 | FKM-B |
| 1 | EPDM |
| 2 | PTFE · elastomer-free |
| 3 | FFKM |
| Field 7 · Communication / version | |
|---|---|
| 000 | Standard version |
| 0M0 | Modbus / RS485 |
| Hlava | PVDF |
| Instalační sada | PVDF |
| Kategorie | Čerpadla |
| Koule | Keramika |
| Krytí | IP65 |
| Max. Průtok | 7 l/h |
| Max. Výtlak | 20 bar |
| Membrána | PTFE |
| Rozměry | 231 x 119 x 145,4 |
| Těsnění | EPDM |
| Typ | Digitální |
| Výrobce | SEKO S.p.A. |
| Zdvih / min | 120 |
| Napětí | 230 V |
| Hadička | 4 x 6 |
This online store stores cookies that help it function properly. By using our services, you agree to their use.